Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM00847
Parcel: 10321025E

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T17CM00847
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Structural Calculations; Sheet 2: The structural calculations for the metal building are the product of the Metallic Building Company. The metal building calculations and drawings must be sealed, signed, and dated by a registered design professional per the IBC Section 107. The registered professional engineer's seal on Sheet 2 of the structural calculations must be signed and dated. Please provide.