Permit Number: T17CM00832
Parcel: 140420740

Address:
7250 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM00832
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2017 ANDREW CONNOR ZONING REVIEW Passed
02/01/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/01/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE. #1. PROVIDE COMPLETE COMPLIANCE WITH THE 2012 IECC FOR THE LIGHTING. #2. THE ELECTRICAL POWER FLOOR PLAN AND THE PANEL SCHEDULE SHOW PANEL 'LPR12' AS EXISTING. THE ONE LINE DIAGRAM SHOWS IT AS A NEW PANEL.
02/01/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
02/01/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/01/2017 ROBERT SHERRY WATER REVIEW Completed
02/01/2017 PBAUGHM1 LANDFILL REVIEW Passed
02/02/2017 MARTIN BROWN FIRE REVIEW Approved
02/02/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approv-Cond
02/02/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/07/2017 ARUIZ1 WWM REVIEW Needs Review