Permit Number: T17CM00796
Parcel: 136254110

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM00796
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2017 MARTIN BROWN FIRE REVIEW Approved
02/22/2017 DAVID RIVERA ZONING REVIEW Approved
03/03/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SUNMODO CORPORATION DRAWINGS: THE FIRST SIX SHEETS INDICATE 'PRELIMINARY DRAWING'. PLEASE REMOVE.
2. SUNMODO CORPORATION DRAWINGS: IT IS NOT CLEAR ON THE DRAWINGS WHERE THE ROOF MOUNT SYSTEMS 3LX5 AND 3LX10 ARE LOCATED. PLEASE CLARIFY.
3. SUNMODO CORPORATION DRAWINGS: PLEASE PROVIDE STRUCTURAL CALCULATIONS TO CONFIRM THE ADEQUACY OF THE PHOTOVOLTAIC HOLDOWN ANCHORS TO RESIST LATERAL LOADS. PROVIDE ANCHOR SIZE, LENGTH, CAPACITY, AND LOCATIONS.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/13/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE PROVIDE FOR A WARNING LABEL AT THE PV LOAD SIDE SOURCE CIRCUIT BREAKER IN THE SERVICE PANEL AS REQUIRED PER NEC ARTICLE 705.12 (D) 7. " DO NOT RELOCATE THIS OVERCURRENT DEVICE"

Final Status

Task End Date Reviewer's Name Type of Review Description
03/20/2017 KROBLES1 OUT TO CUSTOMER Completed