| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/22/2017 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 03/03/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SUNMODO CORPORATION DRAWINGS: THE FIRST SIX SHEETS INDICATE 'PRELIMINARY DRAWING'. PLEASE REMOVE. 2. SUNMODO CORPORATION DRAWINGS: IT IS NOT CLEAR ON THE DRAWINGS WHERE THE ROOF MOUNT SYSTEMS 3LX5 AND 3LX10 ARE LOCATED. PLEASE CLARIFY. 3. SUNMODO CORPORATION DRAWINGS: PLEASE PROVIDE STRUCTURAL CALCULATIONS TO CONFIRM THE ADEQUACY OF THE PHOTOVOLTAIC HOLDOWN ANCHORS TO RESIST LATERAL LOADS. PROVIDE ANCHOR SIZE, LENGTH, CAPACITY, AND LOCATIONS. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/13/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PLEASE PROVIDE FOR A WARNING LABEL AT THE PV LOAD SIDE SOURCE CIRCUIT BREAKER IN THE SERVICE PANEL AS REQUIRED PER NEC ARTICLE 705.12 (D) 7. " DO NOT RELOCATE THIS OVERCURRENT DEVICE" |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/20/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |