Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T17CM00770
Parcel: 13316024L

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM00770
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2017 ANDREW CONNOR ZONING REVIEW Approved
01/31/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
01/31/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE.
#1. Please provide a complete luminaire schedule and IECC code compliance for new or replaced interior lighting. The electrical plan E1.0 refers only to demo work, see notes on plan sheet A2.
#2. If there are electrical modifications for power or data, please clarify on the power and outlet plan.
Ref: 2012 IBC 107.2.1, 2011 NEC, 2012 IECC.
01/31/2017 MARTIN BROWN FIRE REVIEW Approved
01/31/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/31/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/01/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/01/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/01/2017 ROBERT SHERRY WATER REVIEW Completed
02/01/2017 KROBLES1 WWM REVIEW Needs Review