Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM00770
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/31/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 01/31/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 01/31/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE. #1. Please provide a complete luminaire schedule and IECC code compliance for new or replaced interior lighting. The electrical plan E1.0 refers only to demo work, see notes on plan sheet A2. #2. If there are electrical modifications for power or data, please clarify on the power and outlet plan. Ref: 2012 IBC 107.2.1, 2011 NEC, 2012 IECC. |
| 01/31/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/31/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/31/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/01/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 02/01/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 02/01/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/01/2017 | KROBLES1 | WWM | REVIEW | Needs Review |