Permit Number: T17CM00738
Parcel: 13316017B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM00738
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/02/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T17CM00738 - PLAN REVIEW COMMENTS
Reviewer: Chris Anderson, February 1, 2017
BUILDING – COMMERCIAL
On sheet CV, add a visible deferred submittals list, including 1) Trellises, including structural calculations sealed by an Arizona registrant for construction and attachment to existing structure, 2) Canopies/sunscreens, including structural calculations sealed by an Arizona registrant for construction and attachment to existing structure.
On sheet CV, Building Data, delete “/B2”. The IBC does not recognize occupancy group “B2.”
On sheet G0.1, text has been cut off all along the left border of the sheet.
Demolition General Note F on sheet D1.0 instructs contractor bid roof repair; however the Roof Plan and notes on sheet A1.2 indicates that this building will be re-roofed with TPO over new rigid insulation.
Note on detail 3/A1.2 refers reader to sheet A1.3 for roof assembly specification.
On sheet A3.0, New Exterior Storefront Assembly note indicates a required U-factor of 0.57 and SHGC of 0.39. However, 2012 IECC Table C402.3 requires a maximum U-0.50 for fixed fenestration and maximum U-0.83 for entrance doors. The maximum SHGC allowed is 0.25. Revise.
On sheet A3.0, note 6 for both the New Trellis System and New Canopy/Sunscreen System shall indicate that the structural calculations must be sealed by an Arizona registrant.
On sheet S1.0, Structural General Note 7 requires special inspection for wood per IBC 1705.5. 1705.5 requires site built high-load diaphragms and metal-plate-connected wood trusses spanning 60 feet or greater to be special inspected, but there appear to be none on this project. Please clarify in this note what wood assemblies are to be special inspected.
Regarding sheets K-1D and K-3D, the City of Tucson requires that all lettering (upper and lower case) to be a minimum of 3/32” in height. Revise elevations to comply.
Regarding sheets K-1D and K-3D, there are boxed notes from the kitchen equipment designer to the architect that may or may not have been addressed by the Architect. Please verify that they have been satisfied and remove these comments from these sheets.
02/02/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL - COMMERCIAL
On sheet M0.0 the Ventilation Schedule does not appear to have been calculated in accordance with IMC 403.2 and 403.3 requirements and equations. Submit occupant load calculations in accordance with 403.3 and Table 403.3 to support what you have shown in your schedule. Occupancy based on IBC egress is not the same as occupancy based on IMC Table 403.3. Also submit ventilation calculations per IMC 403.3.1.1 through 403.3.2.3.4 to justify total quantity of OA for each occupancy shown in your schedule.
On sheet M1.2, keyed note 11 refers to an as-built mechanical plan. Include as-built mechanical plan in drawing set for reference. Ref. IMC 106.3.1.
Submit mechanical equipment COMcheck.
Regarding sheet M4.1, Rooftop Unit Schedule, submit heating and cooling load calculations summary sheets to justify capacities of the selected equipment, based on winter design dry bulb temperature of 32-degrees F and summer design dry bulb temperature of 104-degrees F and design wet bulb temperature of 66-degrees F (COT amendment to IMC, new section C302.2). The output capacity of heating and cooling equipment and systems shall not exceed the loads calculated in accordance with IECC Section C403.2.1. Ref. 2012 IECC C403.2.2.
Regarding sheet M4.1, Rooftop Unit Schedule, verify that heating and cooling equipment is selected based on performance at 104-degrees F summer design DB temperature and 32-degrees F winter DB design temperature.
02/02/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – COMMERCIAL
The City of Tucson requires that all lettering (upper and lower case) to be a minimum of 3/32” in height. Revise schedules to comply.
Provide interior wattage calculations per 2012 IECC C405.5.2.
Provide outdoor lighting calculations for the parcel per City of Tucson/Pima County Outdoor Lighting Zone. Note that the rated color temperature of light sources shall not exceed 3500K. Ref. OLC 402.1.
On sheet E1.1, indicate which panelboards are new and which are existing. Also show all panels on the electrical power plan. On the riser diagram is appears that panel AP-3 is a new panel. Is this true? Also, the KES panel is not shown on the riser diagram, nor is the breaker size indicated. Provide this information.
02/02/2017 FRODRIG2 WATER REVIEW Reqs Change
02/02/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
On sheet P0.1, Plumbing Fixture Schedule, note that lavatory faucets must be automatic and dispense no more than 0.25 gallon per metering cycle. Ref. COT amendment to 2012 IPC, new section 416.6.
Provide water calculations. Ref. 2012 IPC 106.3.1.
Provide plumbing fixture units schedule and calculations showing existing to remain, new, and removed, with total increase of decrease. Ref. 2012 IPC 106.3.1.
On sheet P1.1, locate grease interceptor and provide calculations to verify capacity for added load. Ref. COT amendment to 2012 IPC, Section 1003.3.
On sheet P1.5, Kitchen Rough-In Plan all equipment is in gray scale. For clarity, define in black line and notes/arrows from key numbers what items are new or relocated. Ref. 2012 IPC 106.3.1.
In reference to Plumbing Schedule, sheet P1.5, appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to 2012 IPC Section 608.13.1 require backflow prevention. Indicate in schedule were required and specify the backflow prevention device required for each water connection. Ref. 2012 IPC 608.1 and 608.3.
02/03/2017 MARTIN BROWN FIRE REVIEW Approved
02/14/2017 DAVID RIVERA ZONING REVIEW Approved
02/15/2017 GERRY KOZIOL WWM REVIEW Reqs Change The following is needed for Sewer Connection Fee Application Approval:



Need PCRWRD/IWC/Steven Valencia review – 520-724-6200 (steven.valencia@pima.gov).