Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM00673
Parcel: 117121900

Address:
40 E CONGRESS ST

Review Status: Completed

Review Details: REVISION - - 6TH

Permit Number - T17CM00673
Review Name: REVISION - - 6TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change If FC-5 is now supplying outside air to the areas previously supplied by FC-FC-3.1, FC-4.1 and FC-5.1, include the total area (stairs plus landings) in the ventilation calculations and update fan coil unit schedule to reflect the total outside airflow. [Initial comment: Fan coil 5-1 is now supplying outside air for the lobby areas formerly ventilated by FC 2-1, FC 3-1, FC 4-1 and FC -5-1. Explain why the scheduled amount of outside air supplied by the four fan coils has not changed from the initial value of 60 CFM each (see fan coil unit schedule) and the total floor area of the lobbies has changed for the ventilation calculations.]
01/29/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change How many urinals are required in the women's restroom? [Initial comment: Relabel rooms 508 and 509 (1/P5.0) to coordinate with the architect.]