Review Status: Completed
Review Details: REVISION - - 6TH
Permit Number - T17CM00673
Review Name: REVISION - - 6TH
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/29/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | If FC-5 is now supplying outside air to the areas previously supplied by FC-FC-3.1, FC-4.1 and FC-5.1, include the total area (stairs plus landings) in the ventilation calculations and update fan coil unit schedule to reflect the total outside airflow. [Initial comment: Fan coil 5-1 is now supplying outside air for the lobby areas formerly ventilated by FC 2-1, FC 3-1, FC 4-1 and FC -5-1. Explain why the scheduled amount of outside air supplied by the four fan coils has not changed from the initial value of 60 CFM each (see fan coil unit schedule) and the total floor area of the lobbies has changed for the ventilation calculations.] |
01/29/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | How many urinals are required in the women's restroom? [Initial comment: Relabel rooms 508 and 509 (1/P5.0) to coordinate with the architect.] |