Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T17CM00673
Parcel: 117121900

Address:
40 E CONGRESS ST

Review Status: Completed

Review Details: REVISION - - 6TH

Permit Number - T17CM00673
Review Name: REVISION - - 6TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Remove orphaned note (1" HW) from the enlarged fourth floor plumbing plan.
2. Keynotes 18 and 19 no longer appear on the fourth floor plumbing plan.
3. Relabel rooms 508 and 509 (1/P5.0) to coordinate with the architect.
01/18/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show how room 209 is being ventilated (sheet M2.0). Reference: Section 401.2, IMC 2012.
2. Fan coil 5-1 is now supplying outside air for the lobby areas formerly ventilated by FC 2-1, FC 3-1, FC 4-1 and FC -5-1. Explain why the scheduled amount of outside air supplied by the four fan coils has not changed from the initial value of 60 CFM each (see fan coil unit schedule) and the total floor area of the lobbies has changed for the ventilation calculations.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2018 QJONES1 APPROVAL SHELF Completed
01/25/2018 QJONES1 OUT TO CUSTOMER Completed
01/25/2018 QJONES1 REJECT SHELF Completed