Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 5TH
Permit Number - T17CM00673
Review Name: REVISION - - 5TH
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/20/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: Please provide an explanation of the changes being made on this revision. This can be done on the drawing or on an 8 1/2 x 11 (sealed, signed, and dated by the engineer of record). 2. General: Please provide two sets of the new calculations with the beam size changes. These need to be sealed, signed, and dated by the engineer of record. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/22/2017 | QJONES1 | APPROVAL SHELF | Completed |
| 12/22/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
| 12/22/2017 | QJONES1 | REJECT SHELF | Completed |