Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM00647
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 04/19/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The structural calculations do not include the weight of a person working on the hood. The hood detail shows the 2"x8" joists located within 18" of the hood (the use of fire wrap on the top of the hood is not allowed per Section 507.10, IMC 2012). [Initial comment: Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 304.1, IMC 2012.] |
| 04/20/2017 | LBOJORQ1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 04/20/2017 | GERRY KOZIOL | WWM | REVIEW | Approved |