Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2017 KEN BROUILLETTE FIRE REVIEW Reqs Change Unable to find a code review analysis. Are fire sprinklers going to be installed? What is going to be stored in the building, and in what quantities?
02/08/2017 DAVID RIVERA ZONING REVIEW Reqs Change Zoning will reviewi the building plans on the next submittal and verify compliance with a revised DP. At this time there is no DP that has been approved for the new building. Also there may be an issue with the possible non-conforming use in this zone which may have to be evaluated by the Zoning Administrator. Contact Steve Shields 837-4956 for more information.
02/10/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide drawings that adequately address the scope of work to be done and demonstrate that the work will conform to all relevant codes. Reference: Section 107.2.1, IBC 2012.
02/10/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide drawings that adequately address the scope of work to be done and demonstrate that the work will conform to all relevant codes. Reference: Section 107.2.1, IBC 2012.
02/10/2017 ROBERT SHERRY WATER REVIEW Reqs Change Provide sufficient information to show that the installation of the new plumbing fixtures will not cause the existing water supply system to become overloaded. Reference: Section 107.2.1, IBC 2012.
02/14/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S1.0 (FOOTING SCHEDULE); STRUCTURAL CALCULATIONS (FOUNDATION DESIGN): THE CALCULATIONS INDICATE FOOTING F1 HAS 5-#5 EACH WAY TOP AND BOTTOM. THE FOOTING SCHEDULE DOES NOT INDICATE TOP AND BOTTOM IN THE REINFORCING, AND REFERENCE SECTIONS 3/S2.0 AND 4/S2.0 DO NOT SHOW TOP AND BOTTOM REINFORCING. PLEASE VERIFY.
2. SHEET S1.0; FOUNDATION PLAN: THERE ARE NO STRUCTURAL CALCULATIONS FOR THE F-2 FOOTINGS INDICATED ON THE PLAN. WHAT ARE THESE FOOTINGS FOR? PLEASE CLARIFY AND ADD STRUCTURAL CALCULATIONS FOR THEIR DESIGN.
3. SHEET S2.0; SECTION 10: PLEASE COMPLETE THE REFERENCE SECTION AT THE SLAB EDGE.
4. METAL BUILDING DRAWINGS/CALCULATIONS: PER THE IBC SECTION 107.3.4.1, DEFERRED SUBMITTAL DOCUMENTS MUST BE SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE AND REVIEWED AND FOUND IN GENERAL CONFORMANCE TO THE BUILDING DESIGN. PLEASE FOLLOW THE REQUIREMENTS OF THAT SECTION.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/15/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
02/22/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE.
#1. REVISE THE ELECTRICAL ONE LINE DIAGRAM TO AN UNDERGROUND FED SERVICE LATERAL. CITY OF TUCSON AMMENDMENT TO THE 2012 IBC, SEC. 112.1. SEC. 112.1.1 REQUIRES ALL NEW CONSTRUCTION TO UTILIZE UNDERGROUND FED ELECTRICAL SERVICE EQUIPMENT.
REF: 2012 IBC, 2011 NEC.
02/24/2017 LOREN MAKUS ENGINEERING REVIEW Needs Review Provide approved Development Package for this project.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/02/2017 LBOJORQ1 OUT TO CUSTOMER Completed