Permit Number: T17CM00460
Parcel: 12310001A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM00460
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2017 MARTIN BROWN FIRE REVIEW Approved For future reference, Tucson is under the 2012 IFC, not UFC
02/09/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T17CM00460 - PLAN REVIEW COMMENTS
Reviewer: Chris Anderson, February 7, 2017
BUILDING – COMMERCIAL
Submit a City of Tucson Code Analysis Data sheet. Is this building a non-separated I-2 or a separated use facility? What is the building type? What is the occupancy group and occupancy load? What is the square footage of affected area?
Submit plumbing fixture calculations and show how suite is in compliance.
On sheet g1.0, change Code Requirement for NEC to 2011 edition, and NFC to 2012 edition.
On sheet g1.3, the new entry alcove indicates a 1-hour rated soffit; however the corridor wall is shown as 2-hour rated. Show alcove soffit/ceiling as 2-hour rated and provide section detail.
On sheet g1.3, remodeled Procedure Room 5 shows perimeter walls as lead-lined. Is the original procedure room lead-lined with a lead lined door? Also, the new work shown in this room shown on sheet a1.0 refers to “5/8” GWB, moisture resistant” (keynote 3) with no mention that it is to be lead lined. Please clarify the work on both sheets. If the doors are to be new lead-lined doors, include them on the door schedule, sheet a4.0.
On sheet S1.0, structural support for hanging equipment is detailed. Submit structural calculations for these point loads imposed on the existing floor/roof structure.
On sheet a1.0, add “2-hr fire rated” to keynote 5.
On sheet a1.0, keynote 16 at corridor wall of procedure room 5 appears to be erroneous.
On sheet a4.0, door and frame schedule, doors 2630A, 2640, 2649, and 2886 should be noted as “90-minute U.L. rating.” Associated hardware sets 1 and 7 should include door closers.
02/09/2017 FRODRIG2 WATER REVIEW Approved PER PIMA COUNTY - CHRIS ANDERSON
02/09/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Approved
02/09/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change BUILDING – ELECTRICAL
Provide occupancy sensors for restrooms 2634 and 2650 per IECC C405.2.2.2.
02/09/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Approved
02/10/2017 GERRY KOZIOL WWM REVIEW Approved