Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM00450
Parcel: 10709009A

Address:
2621 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM00450
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
01/23/2017 KEN BROUILLETTE FIRE REVIEW Approved
01/27/2017 ANDREW CONNOR ZONING REVIEW Approved
02/08/2017 ROBERT SHERRY WATER REVIEW Completed
02/08/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide calculations to show that the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012 for A3 assembly occupancy are being installed.
1. With regard to the water calculation, Tucson Water limits a 1" meter to a maximum demand of 37.5 GPM.
2. Verify the developed pipe length for the water service; the meter is located at the property line and much further than 50-feet.
3. Verify the minimum available water pressure for this address with Tucson Water; the data from Tucson Water appears to show a pressure range of 57 to 64 PSI. Revise the water pressure calculations as required.
4. Revise the water distribution system design criteria to provide a reasonable pressure drop for the reduced pressure zone assembly, typically 10 PSI or as presented by the manufacturer. Reference: Section 604.1, IPC 2012.
5. Provide third-party listing and material standards for all plumbing fixtures being installed. Reference: Sections 303.4 and 402, IPC 2012.
6. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
7. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5, 607.1, and 607.1.2, IPC 2012.
8. Considering the revisions to the existing horizontal drains, clarify how the existing lavatory is to be drained and vented. Reference: Section 107.2.1, IBC 2012.
02/09/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the dimensions of the transfer grilles between the lobby and the chapel; are they 12 x 10 or 14 x 4?
2. Calculation of the required minimum ventilation for air handlers serving multiple zones requires the balancing data (supply CFM) for each zone and the calculations described in Sections 403.3.2.3.1 through 403.3.2.3.4, IMC 2012. Reference: section 403.3.2.3, IMC 2012.
3. Provide justification for the occupant density for the Pulpit (i.e. see Table 403.3, IMC 2012 for an occupancy that is similar with regard to occupant density and activity). Reference: Section 403.3, IMC 2012.
4. Revise the mechanical design as required to avoid using corridor A102 as a return air duct. Reference: Section 601.2, IMC 2012.
5. Show how the duct penetrations will maintain the integrity of the fire-rated floor-ceiling assembly and the fire-rated partition in the lobby. Reference: Sections 607.5.3, and 607.6.1, IMC 2012
02/13/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G003; PLAN C1: A NOTE FOR THE INWARD DOOR SWING REFERENCES THE 2003 ANSI AND SECTION 603.2.3. PLEASE REVISE BOTH REFERENCES.
2. SHEET G003; ELEVATION F1: PLEASE REVISE ALL ADAAG REFERENCES TO PERTINENT REFERENCES IN THE 2009 ICC/ANSI A117.1.
3. SHEET G003; ADA COMPLIANCE NOTES (SIGNAGE): NOTE 2 REFERENCES SECTION 703.2.8 FOR MOUNTING LOCATION. PLEASE REVISE THE REFERENCE.
4. SHEET G003; ADA COMPLIANCE NOTES (SIGNAGE): NOTE 3 REFERENCES SECTION 703.28 FOR SIGN LOCATIONS. PLEASE REVISE THE REFERENCE.
5. SHEET G003; ADA TOILET CLEARANCES PLAN C1: PLEASE REVISE THE UNI-SEX TOILET ROOM LAYOUT AND THE SINGLE TOILET ROOM LAYOUT TO MATCH THE RESTROOM LAYOUTS INDICATED ON SHEET A110.
6. SHEET G004; OCCUPANCY ANALYSIS TABLE: PLEASE VERIFY THE OCCUPANT LOAD FOR ROOM 107 (OFFICE). A 300 SF/OCCUPANT ALLOWANCE WAS USED RATHER THAN THE TYPICAL 100 SF/OCCUPANT.
7. SHEET G004; CODE ANALYSIS (OCCUPANCY SEPARATION): PLEASE INDICATE ON THE DRAWING THE A3 ASSEMBLY AREA DOES NOT REQUIRE AN AUTOMATIC SPRINKLER SYSTEM PER THE IBC SECTION 903.2.1.3.
8. SHEET G004; LIFE SAFETY PLAN (LEVEL 2): PLEASE REVISE THE MEZZANINE AREA REQUIREMENT (INDICATED ON THE PLAN) TO INDICATE
(217 + 169)/1172 = 33%.
9. SHEET G004; LIFE SAFETY PLAN (LEVEL 2): A NOTE ON THE PLAN INDICATES '45% FREE AREA BETWEEN MEZZANINE AND CHAPEL'. IS THIS THE OPEN AREA IN THE WALL? PLEASE CLARIFY, AND NOTE THIS MEETS THE REQUIREMENTS OF THE IBC SECTION 505.2.3 (EXCEPTION 2).
10. SHEET G004; FLOOR PLAN (LEVEL 1): SHOULD THE CORRIDOR A102 BE REQUIRED TO HAVE A ONE HOUR FIRE RESISTANCE RATING PER THE IBC TABLE 1018.1 (ASSEMBLY OCCUPANCY WITH OCCUPANT LOAD SERVED OF GREATER THAN 30)? PLEASE VERIFY.
11. SHEET G004; FLOOR PLAN (LEVEL 1): AT THE NOTES INDICATING A ONE HOUR FIRE RESISTANCE RATING AT WALLS AND AT CEILING/FLOOR ASSEMBLY, PLEASE ADD TO REFERENCE SHEETS A110 AND A701 FOR THE UL LISTING NUMBER AND CONSTRUCTION. IN ADDITION, REFERENCE THE DOOR SCHEDULE ON SHEET A700 FOR FIRE RESISTANCE RATINGS REQUIRED.
12. SHEET G004; CODE ANALYSIS (EXIT TRAVEL DISTANCE): THE DRAWING INDICATES A MAXIMUM TRAVEL DISTANCE OF 100'-0" WITHOUT SPRINKLERS PER THE IBC TABLE 1016.2. SHOULD THIS BE 200'-0"? PLEASE VERIFY.
13. SHEET G004; CODE ANALYSIS (NUMBER OF EXITS): A REFERENCE ON THE DRAWING INDICATES TABLE 1021.2(2) APPLIES ONLY TO LEVEL 2. THIS TABLE IS APPLICABLE ONLY FOR STORIES WITH ONE EXIT OR ONE EXIT ACCESS. DOES THIS APPLY SINCE THERE ARE TWO EXITS AT THE MEZZANINE LEVEL? PLEASE VERIFY.
14. SHEET A110; FLOOR PLAN (LEVEL 1): IN THE AUTO REPAIR BAY (A106), OFFICE (A107), AND STORAGE (A108) AREAS, PLEASE INDICATE "NO WORK THIS AREA".
15. SHEET A110; FLOOR PLAN A1: PLEASE INDICATE ON THE PLAN THAT THE NEW RAMP LANDINGS MEET THE REQUIREMENTS OF THE IBC SECTION 1010.7 FOR LANDING SIZE AND SLOPE.
16. SHEET A110; FLOOR PLAN A1: NEW GUARDRAIL AND HANDRAIL ARE INDICATED AT THE NEW RAMP. GUARDRAILS ARE REQUIRED ONLY WHERE THE WALKING SURFACE IS LOACTED MORE THAN 30" ABOVE THE FLOOR OR GRADE ADJACENT TO THAT SURFACE (IBC SECTION 1013.2). PLEASE REVISE THE PLAN NOTE ON SHEET A110 AND THE TITLE OF DETAIL A7/A300.
17. SHEET A110 (LEVEL 1 FLOOR PLAN); SHEET A700 (DOOR SCHEDULE): DOOR A101 SHOULD INDICATE A RATED DOOR IN THE SCHEDULE. PLEASE VERIFY.
18. SHEET A110 (LEVEL 1 FLOOR PLAN); SHEET A700 (DOOR SCHEDULE): DOORS A102A AND A103 SHOULD INDICATE RATED DOORS IN THE SCHEDULE IF IT IS DETERMINED CORRIDOR A102 SHOULD BE RATED. PLEASE VERIFY.
19. SHEET A300; DETAILS A3, A5, AND A7: PLEASE REVISE THE HANDRAIL HEIGHTS TO MEET THE REQUIREMENTS OF THE IBC SECTION 1012.2 (34" TO 38").
20. SHEET A300; DETAILS A3, A5, AND A7: PLEASE INDICATE THE NEW CONCRETE SLAB THICKNESS AND REINFORCING.
21. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/14/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/15/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment.
#1. Provide full compliance with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE for the exterior lighting.
02/18/2017 GERRY KOZIOL WWM REVIEW Completed P17WX00121