Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM00409
Parcel: 116274690

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T17CM00409
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2019 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/20/2019 QJONES1 APPROVAL SHELF Completed
05/20/2019 QJONES1 OUT TO CUSTOMER Completed
05/20/2019 QJONES1 REJECT SHELF Completed