Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM00407
Parcel: 11310005A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM00407
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/24/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments.
#1. Revise the water heater circuits to the correct circuit numbers.
#2. Identify the symbol ( fuse ) between the service and the new panel, also the OCPD is oversized for the new panel ampacity rating.
Ref: 2012 IBC 107.2.1, 2011 NEC 408.
01/25/2017 LBOJORQ1 WATER REVIEW Needs Review
01/25/2017 LBOJORQ1 PLUMBING-COMMERCIAL REVIEW Needs Review
01/25/2017 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/25/2017 LBOJORQ1 MECHANICAL-COMMERCIAL REVIEW Needs Review