Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM00407
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/24/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/24/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. #1. Revise the water heater circuits to the correct circuit numbers. #2. Identify the symbol ( fuse ) between the service and the new panel, also the OCPD is oversized for the new panel ampacity rating. Ref: 2012 IBC 107.2.1, 2011 NEC 408. |
| 01/25/2017 | LBOJORQ1 | WATER | REVIEW | Needs Review | |
| 01/25/2017 | LBOJORQ1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 01/25/2017 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 01/25/2017 | LBOJORQ1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review |