Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/17/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
01/17/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide cooling/heating load calculations for the new water source heat pumps. Show that they comply with the requirements of the IECC. 2. The ventilation calculations call for 100 CFM of exhaust from the pathology lab but no exhaust is provided. |
01/17/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
01/17/2017 | DTAKAKI1 | ENGINEERING | REVIEW | Approved | |
01/17/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/17/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
01/17/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/18/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
01/31/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
01/31/2017 | GERRY KOZIOL | WWM | REVIEW | Approved |