Permit Number: T17CM00167
Parcel: 10320075B

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL TI

Permit Number - T17CM00167
Review Name: 3RD PARTY REVIEW - COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2017 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Completed
04/25/2017 FRODRIG2 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Approved
04/26/2017 ROBERT SHERRY WATER REVIEW Completed
04/26/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Via Elegante -Tucson Mountains
T17CM00167
Building Plan (1st Review)

TRANSMITTAL DATE: April 26, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Until the revision to development package DP16-0168 has been approved the building plans cannot be approved.

3. The development package sheets provided in the building plan either need to be; the signed approved development package, marked as for reference only, or removed from the building plan set.

4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
04/28/2017 MARTIN BROWN FIRE REVIEW Reqs Change On sheet A4.1.4, item 2 indicates a type 2 hood. For commercial applications utilizing appliances that could create
grease laden vapors, a type 1 hood with a suppression system is required. Please revise.
Please add fire alarm plans and kitchen exhaust hood fire suppression plans to list of deferred submittal on sheet T1.0.
05/02/2017 FRODRIG2 WWM REVIEW Reqs Change The following is needed for Sewer Connection Fee Application Approval:

Need PCRWRD/IWC/Steven Valencia’s review of 500 gallon interceptor per drawing P1.1

(Steven.valencia@pima.gov - 520-724-6200)

Need to clarify existing water meter (serial number, size & location) for sewer connection fee review.

*water meter #21281644 shown on plumbing calculations P3.0 is a 6” water meter for fire sprinklers with no sewer user fees attached.
05/02/2017 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/03/2017 KROBLES1 OUT TO CUSTOMER Completed