Permit Number: T17CM00085
Parcel: 11206424A

Address:
2545 N TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T17CM00085
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2017 MARTIN BROWN FIRE REVIEW Approved
01/24/2017 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T17CM00085 - Proposed Expansion Crematory
Building Plan Review (1st Review)
2545 N Tucson Blvd. - Funeral Services Use

TRANSMITTAL DATE: January 24, 2017

DUE DATE: February 14, 2017

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans as it relates to the zoning review purview, footprint, building heights, etc.


2. COMMENT: Prior to approval of the building plans by zoning, an approved Development Package will be required. As of this building review no application/development package has been submitted for review. Zoning will review the building plans on the next submittal for compliance with an approved DP.


3. COMMENT: A few of the sheets in the building package were not located as listed in the sheet index. Verify that the sheet index matches the sheet number or that the sheets are stapled as listed in the index.


4. COMMENT: As part of the building review zoning reviewed the site plan sheet for consistency with the actual site and it does not appear that the site plan matches the actual site. Review the site plan and the physical location and revise for consistency.


5. COMMENT: Additional comments may be forthcoming based on the response to the zoning comments and revisions to the building plans.


If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

David Rivera can reached Tuesday and Wednesday from 8:00 to 5:00 at (520) 837-4957 or at David.Rivera@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised building plan package
01/26/2017 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change A development package that reflects the existing and proposed layout of the site is required.
02/01/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change BUILDING – ELECTRICAL
New exterior light fixtures are proposed. Submit lumen calculations for this parcel to show compliance with 2012 City of Tucson/Pima County Outdoor Lighting Code. Lighting area is E3.
Submit interior lighting wattage calculations per IECC C405.5.2.
On sheet EL111, add occupancy sensors for crematory back room 119.
02/01/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Approved
02/01/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T17CM00085 - PLAN REVIEW COMMENTS
Reviewer: Chris Anderson, January 31, 2017
BUILDING – COMMERCIAL
In the next submittal relocate structural schedules (sheet AY702) with engineer’s seal to follow structural sheets SF111 and SR111.
On sheet SR111, there is a note “4” minimum framing standoff from chimney.” This may not be sufficient clearance to combustibles. 4” clearance is sufficient for masonry fireplaces per IBC 2111; however IMC 907.1 states that crematories shall be listed and labeled and shall be installed and terminated in accordance with the manufacturer’s installation instructions. Submit crematory manufacturer’s installation requirements pertaining to chimney clearance to combustibles and installation through a combustible roof.
On sheet AR111, note 2 above applies to chimney detail G1. The metal flashing attached to both the flue and combustible curb could potentially be a fire hazard. In addition, the clearance to combustible shown is different from that shown on the framing plan. It is likely that the manufacturer will require a sheet metal thimble and storm collar assembly to separate all parts of the chimney from combustibles, and made to specific dimensions to maintain required clearances. Revise detail to comply with manufacturer’s instructions.
On sheet AW300, there is a note “maintain 1” clr standoff of wall to crematory all around.” Submit manufacturer’s installation instructions to confirm that this clearance to combustible construction is adequate.
On sheets AW300 and AX501 details indicate R-30 roof insulation; however IECC Table C402.2 requires minimum R-38 roof insulation. Either change insulation to R-38 or submit a COMcheck for the proposed thermal envelope indicating that it meets energy requirements of the Code.
On sheet AX501, revise note on details A1 and A5, “Stucco weep screed. Locate minimum 2” above paving and minimum 4” above ground surface.” Reference IBC 2512.1.2.
On sheet AY701, revise door schedule note 2 to add, “Overhead door to have a minimum R-4.75.” Ref. IECC Table C402.2.
On sheet AY701, add door schedule note 5, “Maximum U-factor for exterior swinging door is U-0.61.” Add this note reference for door 116B1 in the door schedule Notes column.
02/01/2017 FRODRIG2 WATER REVIEW Passed
02/01/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Approved
02/01/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/13/2017 KROBLES1 OUT TO CUSTOMER Completed