Permit Number: T17CM00007
Parcel: 11005557A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM00007
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2017 MARTIN BROWN FIRE REVIEW Approved
02/10/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE.
#1. REF: PLAN SHEET PV5.
The PV point of interconnection shall comply with 690.64, 705.12, 705.12D1. This is not a line side tap, but a load side interconnection as the proposed tap is downstream of the 200 amp service disconnecting means.
#2. Please clarify in detail the distance between equipment and wiring methods intended for the conductors shown with the note, "CONDUTORS IN FREE AIR".
REF: 2012 IBC 107.2.1, 2011 NEC .
02/10/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/16/2017 KROBLES1 OUT TO CUSTOMER Completed