Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T17CM00007
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/18/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/10/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE. #1. REF: PLAN SHEET PV5. The PV point of interconnection shall comply with 690.64, 705.12, 705.12D1. This is not a line side tap, but a load side interconnection as the proposed tap is downstream of the 200 amp service disconnecting means. #2. Please clarify in detail the distance between equipment and wiring methods intended for the conductors shown with the note, "CONDUTORS IN FREE AIR". REF: 2012 IBC 107.2.1, 2011 NEC . |
| 02/10/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/16/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |