Permit Review Detail
Review Status: Completed
Review Details: POOL - COMM MODEL
Permit Number - T17BU00465
Review Name: POOL - COMM MODEL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/03/2017 | MGAYOSS1 | ZONING | REVIEW | Needs Review | |
| 10/03/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 10/04/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 10/04/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete electrical plans to include: (a) Minimum text (font) size is required to be 3/31". (b) Electrical plans to be sealed and signed by an electrical engineer registered in the state of Arizona. . Designing the site Electrical constitutes the practice of engineering. Provide plans sealed by an Arizona Registrant. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304 (c) Complete panel schedule including load calcs. (d) Show all grounding required per 2011 NEC art. 680. (e) Provide branch circuit and panel designations for all the pool electrical equipment, including lighting, and luminaire schedule. (f) Complete compliance with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE. SEC.104, 401.2.1 Ref: 2012 IBC sec 107.2.1, 2011 NEC |
| 11/09/2017 | ARUIZ1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/09/2017 | ARUIZ1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |