| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/17/2018 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Reqs Change | Below are the BRC comments on the electrical repair resubmittal for COT ID# 593 at 9801 East Interstate 10 (T17BU00402 RR). Sheet 1 of 2 1. Comment #1 on the original submittal was not responded to. Add dimension to aerial photograph underlay site plan from billboard structure to east parcel boundary along with APN of parcel to east (due to distance, can be shown off the underlay with a break in dimension line); Comment #1 on the original submittal was not responded to. Sheet 2 of 2 1. In Partial Vicinity Map, correct distance from billboard structure to Houghton Road; the revision in response to the Comment #7 on the original submittal is not correct as the 1.0 mile distance provided is in the vicinity of the second of two other billboards located west of the subject billboard. 2. In title for Scop0e of Work strike “Replace” and insert “Reinstall”, to conform with the text provided. FIN. |