Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD - BLDG30days
Permit Number - T17BU00169
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/25/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/17/2017 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Reqs Change | Below are comments on the authorized repair submittal for COT ID# 112 at 7299 South Houghton Road (T17BU00169). Sheet 1 of 2 1. In Billboard Note #3 and aerial photograph overlay plan, delete reference to S-2007-01 and insert City of Tucson Right-of-Way (S-2007-001 is a plan for an area far distant from this location; for any further detail on the subject portion of City right-of-way, reference the right-of-way conveyance recorded in the Pima County Recorder’s office on May 4, 2012). 2. Add note acknowledging that issuance of Permit under terms of the Stipulation does not constitute City permission to occupy City right-of-way. 3. In aerial photograph overlay plan detail, add dimensions from right-of-way line to extremities of billboard footprint. Sheet 2 of 2 1. Add standard details: Stringer Between Uprights and Stringer Mounting Details. FIN. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/28/2018 | KROBLES1 | OUT TO CUSTOMER | Completed |