Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD - BLDG30days
Permit Number - T17BU00104
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/30/2017 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Reqs Change | Below are BRC comments on the authorized repair submittal for COT ID# 346 at 5703 East Speedway Boulevard (T17BU00104). Sheet 1 of 3 1. Revise APN number in Billboard Note #3 and in Title Block (to reflect 2012 & 2013 property changes). Sheet 2 of 3 1. In 1st sentence of boxed note above Scope of Work, add “of the Stipulation”. 2. In 2nd paragraph of Scope of Work, clarify if the non-standard number of carriage bolts per stringer stated (6) is correct or otherwise revise. 3. Add note replicating Billboard Note #11 on Sheet 1 of 3 (as to removal of light fixtures from site). Sheet 3 of 3 1. In Poster Panel Top View, indicate light fixture/support arm assembly to be temporarily detached and then reattached. FIN. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/01/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |