Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD - BLDG30days
Permit Number - T17BU00102
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET 2; SOUTH SIGN FACE ELEVATION: A NOTE AT THE SUPPORT POSTS (COLUMNS) REFERENCES 'EXISTING STRINGERS TO REMAIN'. PLEASE REVISE THE REFERENCE. |
| 03/14/2017 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Reqs Change | Below are the BRC comments on the authorized repair submittal for COT ID# 491 at 3782 North Oracle Road (T17BU00102). Sheet 1 of 2 No comments. Sheet 2 of 2 1. In 1st sentence in first boxed note below Scope of Work, add “of the Stipulation”. 2. Add note replicating Billboard Note #11 on Sheet 1. 3. In South Sign Face Elevation, indicate disposition of face support stringers. 4. In South Sign Face Elevation, correct designation for supporting I-beams (submittal indicates “Stringers”). FIN. |