Permit Number: T17BU00101
Parcel: 11518023A

Address:
1333 N ORACLE RD

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T17BU00101
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/10/2017 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Reqs Change Below are the BRC comments on the authorized repair submittal for COT ID# 511 at 1333 North Oracle Road (T17BU00101).



Sheet 1 of 4



No comments.



Sheet 2 of 4



1. In Scope of Work, combine confusing boxes that separate paragraphs of south face work.



2. In 3rd and/or 6th paragraphs in Scope of Work section for south face, clarify whether 16 d nail attachment of metal face panels is existing method of attachment or a proposed alteration and if there are pre-drilled nail holes on the panels or the nails are driven through the panels; also include the number of nails per metal face panel section.



Sheet 3 of 4



1. In South Sign Face Elevation, clarify what “N/F” and “S/F” means as to light fixtures.



2. In South Sign Face Elevation or other appropriate detail, provide the horizontal measures from the outer panel edges to the nearest upright centers.



3. In South Sign Face Elevation, correct the understated height.



4. In Poster Panel Side View depict entire support arm and light fixture and provide measurement from vertical point of attachment to outer horizontal extremity of light fixture



Sheet 4 of 4



No comments.



FIN.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/21/2017 KROBLES1 OUT TO CUSTOMER Completed