| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/25/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/12/2017 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Reqs Change | Below are comments on the authorized repair resubmittal for COT ID# 593 at 9801 East Interstate 10 (T17BU00055 R). Sheet 1 of 2 No comments. Sheet 2 of 2 1. In 3rd paragraph of Scope of Work, reduce number of stringer pieces from 11 to 10 or otherwise explain the additional stringer compared to the original submittal (12 total in original submittal, including two shorter bottom stringers; now a total of 13). 2. In 8th paragraph of Scope of Work, reduce lengths of lowest 2 pieces of 12 replacement stringer pieces, consistent with the lengths of those to be removed per 3rd paragraph. 3. Revise 2nd paragraph in 1st boxed note below Scope of Work on removal of light fixtures from site to replicate Billboard Note #11 on Sheet 1 per Comment #6 on Sheet 2 of the original submittal (the provided note has a different meaning than the long established language in Billboard Note #11 and is in conflict with Billboard Note #11). 4. In Side View, add depiction of lower backrail (consistent with that now shown in East Sign Face Elevation). FIN. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/21/2017 | AHINES2 | OUT TO CUSTOMER | Completed |