Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD - BLDG30days
Permit Number - T17BU00055
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/16/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/10/2017 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Reqs Change | Below are BRC comments on the authorized repair submittal for COT ID# 593 at 9801 East Interstate 10 (T17BU00055). Sheet 1 of 2 No comments. Sheet 2 of 2 1. In 1st sentence in boxed note above Scope of Work, add “of the Stipulation”. 2. Add two paragraphs to reflect removal and reinstallation or other disposition of light fixtures and light fixture support arms, indicating point of disconnect. 3. In 3rd & 6th paragraphs, revise stringer lengths to reflect shorter bottom stringer. 4. In 4th and/or 5th paragraph of Scope of Work, reference lower backrail and clarify whether it is to be remain in place, removed and reinstalled, or removed and not replaced 5. In the 7th & 8th paragraphs, specify that the plywood panels apron sections are to be attached to the wood stringers and the on centers for the 16d nail attachments. 6. Add note replicating Billboard Note #11 on Sheet 1. 7. In East Sign Face Elevation add depiction of lower backrail (in a fashion similar to that for upper backrail) and indicate its disposition. 8. In East Sign Face Elevation, depict light fixtures. 9. Add light fixture support arm mounting details. FIN. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/17/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |