Plan Number: T16PI00009
Parcel: Unknown

Address:
1002 E 36TH ST

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T16PI00009
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2016 ZELIN CANCHOLA DOT TRAFFIC REVIEW Reqs Change July 22, 2016
ACTIVITY NUMBER: T16PI00009
PROJECT NAME: The Bridges - Block 1
PROJECT ADDRESS: 36th street Park Avenue to Kino Parkway
PROJECT REVIEWER: Zelin Canchola TDOT

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan therefore a revised plan is required for re-submittal. The following items must be revised or added to the plan. Include a response letter with the next submittal that states how all comments have been addressed.

Sheet 8 of 23:

1. List Quantities and descriptions for striping materials lineal footage quantities of longitudinal and traverse striping arrows. (From #24 pavement materials plan review checklist)

Sheet 9 of 23:

1. Change striping at intersection of 36th and park Avenue, and 36th and Kino to YDS4-D40/D40 as shown on redlines.

2. Eliminate striping adjacent to Fremont Avenue.


If you have any questions, I can be reached at 520 837 6659 or zelin.canchola@tucsonaz.gov
07/22/2016 LINZUNZA UTILITY CLEARANCES COT STREETS DIVISION Completed
07/22/2016 LINZUNZA UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
07/22/2016 LINZUNZA UTILITY CLEARANCES PC WASTEWATER MGMT Completed
07/22/2016 LINZUNZA UTILITY CLEARANCES QUEST COMMUNICATION Completed
07/22/2016 LINZUNZA UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
07/22/2016 LINZUNZA UTILITY CLEARANCES COX COMMUNICATION Completed
07/22/2016 LINZUNZA UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
07/22/2016 LINZUNZA UTILITY CLEARANCES EL PASO NATURAL GAS Completed
07/22/2016 LINZUNZA UTILITY CLEARANCES KINDER MORGAN ENERGY Completed
08/09/2016 RICHARD LEIGH DOT ENGINEERING REVIEW Denied August 8, 2016

SUBJECT: Paving Plans for 36th Street - Park Avenue to Kino Boulevard

PROJECT REVIEWER: Richard Leigh, TDOT, TDOT Eng. Review

RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to resubmittal. Please include a response letter addressing the following comments and return redlined drawings with subsequent submittal.

1. Include the plan number "I-2016-007" in the title block of each sheet.

2. Include the PIA activity number "T16PI00009" on cover sheet.

3. Sheet 1: Add Arizona Blue Stake 811 label to cover sheet.

4. Sheet 2, General paving note 13: Change the phone number for Paul Rosenboom to 419-7064.

5. Sheet 3: Clearly demonstrate how flows leaving the proposed sidewalk scupper located at Sta. +/- 23+27, RT 36th St. will be contained in the Rip-Rap blanket. A channel with a curb opening may be required. Please see attached example of a curb opening used on other City projects.

6. Sheet 4 - 6, Paving Plan Keynote No. 17: It's TDOT's policy to perform mill and inlays in lieu of placing pavement overlays. Provide complete details on any proposed pavement surface treatment.

7. Sheet 5: Indicate the placement of an opening in the proposed traffic delineators for pedestrian traffic on the SW corner of 36th St and M.L.K. Blvd. Additionally, provide details of the traffic delineators and installation requierments.

8. Sheet 6: Revise drawing to extend the pedestrian circulation path all the way to Kino Parkway Per Section C.2.4C.i.b.ii of the Bridges Planned Area Development document.

9. Sheet 6: Revise drawing to indicate that the sections of curb which has a curb reveal of less than 6" will need to be removed and replaced. There are sections of curb between Sta. +/-32+40, RT 36th St. and +/-34+70, RT 36th St. where the curb reveal is only 3".

10. Indicate the closure of the existing curb opening located at Sta. 35+60, RT 36th St.

If you have any questions, I can be reached at 837-6647 or emailed at Richard.Leigh@tucsonaz.gov.
08/12/2016 GARY WITTWER DOT LANDSCAPE REVIEW Approved
08/12/2016 LINZUNZA DOT MAPS & RECORDS REVIEW Approv-Cond 1) At pre-con meeting, provide copy of filled-out NOI that was sent to ADEQ.
08/19/2016 LINZUNZA DOT PERMITS & CODES REVIEW Denied Date: August 19, 2016
PROJECT NAME: 36th St: Park Av to Kino Pkwy Offsite Plans for the Bridges - Block 1
PLAN #: I-2016-007
ACTIVITY No: T16PI00009
PROJECT REVIEWER: Lance Peterson, City of Tucson DOT PIA Inspection Unit

Comments:

The TDOT PIA Inspection Unit has reviewed the PIA plan and recommends resubmittal. The following comments need to be addressed prior to submitting the mylar plan set for final approval.

1. Sheet 2 - Note 3 - Asphalt shall conform to the City of Tucson TDOT mixes.
2. Sheet 3 Detail D - Should call out TDOT #2 mix
3. Sheet 7 Detail C - path should call out TDOT #3 mix

If you have any questions, I can be reached at 837-6777 or Lance.Peterson@tucsonaz.gov
08/23/2016 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved
08/24/2016 ERNIE ENCINAS DOT_ELEC REVIEW Approved
08/24/2016 LINZUNZA PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
08/24/2016 LINZUNZA PIA COORDINATOR OUT TO CUSTOMER Completed