Plan Review Detail
Review Status: Completed
Review Details: PIA - SUBMITTAL
Plan Number - T16PI00009
Review Name: PIA - SUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/22/2016 | ZELIN CANCHOLA | DOT TRAFFIC | REVIEW | Reqs Change | July 22, 2016 ACTIVITY NUMBER: T16PI00009 PROJECT NAME: The Bridges - Block 1 PROJECT ADDRESS: 36th street Park Avenue to Kino Parkway PROJECT REVIEWER: Zelin Canchola TDOT Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan therefore a revised plan is required for re-submittal. The following items must be revised or added to the plan. Include a response letter with the next submittal that states how all comments have been addressed. Sheet 8 of 23: 1. List Quantities and descriptions for striping materials lineal footage quantities of longitudinal and traverse striping arrows. (From #24 pavement materials plan review checklist) Sheet 9 of 23: 1. Change striping at intersection of 36th and park Avenue, and 36th and Kino to YDS4-D40/D40 as shown on redlines. 2. Eliminate striping adjacent to Fremont Avenue. If you have any questions, I can be reached at 520 837 6659 or zelin.canchola@tucsonaz.gov |
| 07/22/2016 | LINZUNZA | UTILITY CLEARANCES | COT STREETS DIVISION | Completed | |
| 07/22/2016 | LINZUNZA | UTILITY CLEARANCES | COT WATER NEW DEVELOPMENT | Completed | |
| 07/22/2016 | LINZUNZA | UTILITY CLEARANCES | PC WASTEWATER MGMT | Completed | |
| 07/22/2016 | LINZUNZA | UTILITY CLEARANCES | QUEST COMMUNICATION | Completed | |
| 07/22/2016 | LINZUNZA | UTILITY CLEARANCES | TUCSON ELECTRIC POWER CO | Completed | |
| 07/22/2016 | LINZUNZA | UTILITY CLEARANCES | COX COMMUNICATION | Completed | |
| 07/22/2016 | LINZUNZA | UTILITY CLEARANCES | SOUTHWEST GAS CORP | Completed | |
| 07/22/2016 | LINZUNZA | UTILITY CLEARANCES | EL PASO NATURAL GAS | Completed | |
| 07/22/2016 | LINZUNZA | UTILITY CLEARANCES | KINDER MORGAN ENERGY | Completed | |
| 08/09/2016 | RICHARD LEIGH | DOT ENGINEERING | REVIEW | Denied | August 8, 2016 SUBJECT: Paving Plans for 36th Street - Park Avenue to Kino Boulevard PROJECT REVIEWER: Richard Leigh, TDOT, TDOT Eng. Review RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to resubmittal. Please include a response letter addressing the following comments and return redlined drawings with subsequent submittal. 1. Include the plan number "I-2016-007" in the title block of each sheet. 2. Include the PIA activity number "T16PI00009" on cover sheet. 3. Sheet 1: Add Arizona Blue Stake 811 label to cover sheet. 4. Sheet 2, General paving note 13: Change the phone number for Paul Rosenboom to 419-7064. 5. Sheet 3: Clearly demonstrate how flows leaving the proposed sidewalk scupper located at Sta. +/- 23+27, RT 36th St. will be contained in the Rip-Rap blanket. A channel with a curb opening may be required. Please see attached example of a curb opening used on other City projects. 6. Sheet 4 - 6, Paving Plan Keynote No. 17: It's TDOT's policy to perform mill and inlays in lieu of placing pavement overlays. Provide complete details on any proposed pavement surface treatment. 7. Sheet 5: Indicate the placement of an opening in the proposed traffic delineators for pedestrian traffic on the SW corner of 36th St and M.L.K. Blvd. Additionally, provide details of the traffic delineators and installation requierments. 8. Sheet 6: Revise drawing to extend the pedestrian circulation path all the way to Kino Parkway Per Section C.2.4C.i.b.ii of the Bridges Planned Area Development document. 9. Sheet 6: Revise drawing to indicate that the sections of curb which has a curb reveal of less than 6" will need to be removed and replaced. There are sections of curb between Sta. +/-32+40, RT 36th St. and +/-34+70, RT 36th St. where the curb reveal is only 3". 10. Indicate the closure of the existing curb opening located at Sta. 35+60, RT 36th St. If you have any questions, I can be reached at 837-6647 or emailed at Richard.Leigh@tucsonaz.gov. |
| 08/12/2016 | GARY WITTWER | DOT LANDSCAPE | REVIEW | Approved | |
| 08/12/2016 | LINZUNZA | DOT MAPS & RECORDS | REVIEW | Approv-Cond | 1) At pre-con meeting, provide copy of filled-out NOI that was sent to ADEQ. |
| 08/19/2016 | LINZUNZA | DOT PERMITS & CODES | REVIEW | Denied | Date: August 19, 2016 PROJECT NAME: 36th St: Park Av to Kino Pkwy Offsite Plans for the Bridges - Block 1 PLAN #: I-2016-007 ACTIVITY No: T16PI00009 PROJECT REVIEWER: Lance Peterson, City of Tucson DOT PIA Inspection Unit Comments: The TDOT PIA Inspection Unit has reviewed the PIA plan and recommends resubmittal. The following comments need to be addressed prior to submitting the mylar plan set for final approval. 1. Sheet 2 - Note 3 - Asphalt shall conform to the City of Tucson TDOT mixes. 2. Sheet 3 Detail D - Should call out TDOT #2 mix 3. Sheet 7 Detail C - path should call out TDOT #3 mix If you have any questions, I can be reached at 837-6777 or Lance.Peterson@tucsonaz.gov |
| 08/23/2016 | JIM FEMLING | DOT STREET MAINTENANCE | REVIEW | Approved | |
| 08/24/2016 | ERNIE ENCINAS | DOT_ELEC | REVIEW | Approved | |
| 08/24/2016 | LINZUNZA | PIA COORDINATOR | CUSTOMER CALLED; PLANS @ AMBASSSADOR | Completed | |
| 08/24/2016 | LINZUNZA | PIA COORDINATOR | OUT TO CUSTOMER | Completed |