Plan Number: T16PI00005
Parcel: Unknown

Review Status: Completed

Review Details: PIA - RESUBMITTAL

Plan Number - T16PI00005
Review Name: PIA - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2016 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Completed
06/20/2016 LINZUNZA UTILITY CLEARANCES COT STREETS DIVISION Completed
06/20/2016 LINZUNZA UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
06/20/2016 LINZUNZA UTILITY CLEARANCES PC WASTEWATER MGMT Completed
06/20/2016 LINZUNZA UTILITY CLEARANCES QUEST COMMUNICATION Completed
06/20/2016 LINZUNZA UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
06/20/2016 LINZUNZA UTILITY CLEARANCES COX COMMUNICATION Completed
06/20/2016 LINZUNZA UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
06/20/2016 LINZUNZA UTILITY CLEARANCES EL PASO NATURAL GAS Completed
06/20/2016 LINZUNZA UTILITY CLEARANCES KINDER MORGAN ENERGY Completed
06/22/2016 ZELIN CANCHOLA DOT TRAFFIC REVIEW Approved
06/23/2016 RICHARD LEIGH DOT ENGINEERING REVIEW Approved
06/24/2016 GARY WITTWER DOT LANDSCAPE REVIEW Approved
07/12/2016 LINZUNZA DOT PERMITS & CODES REVIEW Approved
07/25/2016 LINZUNZA PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
07/25/2016 ERNIE ENCINAS DOT_ELEC REVIEW Approv-Cond Sheet 11 of 12,

Note 13 should read, A 14AWG IMSA-19-1984 7- Conductor solid wire cable shall be installed from each traffic signal terminal strip to associated mastarm signal head.

Note 2 in Conductor notes should read, Intersection lighting wire splicing shall only occur within a pullbox and shall be made per standard specifications.

Note 5 in Conductor notes should read, The contractor shall install new IMSA 16 conductor cables from the controller to the terminal block in the sidemount indication, unspliced. Outer cable jacket shall not be removed at handhole height.

Add Note 6 as follows, All existing conductors shall be removed and replaced with new conductors per conduit and conductor schedule sheet 12 of 12.
07/25/2016 LINZUNZA PIA COORDINATOR OUT TO CUSTOMER Completed