Plan Number: T16PI00005
Parcel: Unknown

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T16PI00005
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2016 LINZUNZA UTILITY CLEARANCES COT STREETS DIVISION Denied
04/18/2016 LINZUNZA UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied
04/18/2016 LINZUNZA UTILITY CLEARANCES PC WASTEWATER MGMT Denied
04/18/2016 LINZUNZA UTILITY CLEARANCES QUEST COMMUNICATION Denied
04/18/2016 LINZUNZA UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied
04/18/2016 LINZUNZA UTILITY CLEARANCES COX COMMUNICATION Denied
04/18/2016 LINZUNZA UTILITY CLEARANCES SOUTHWEST GAS CORP Denied
04/18/2016 LINZUNZA UTILITY CLEARANCES EL PASO NATURAL GAS Denied
04/18/2016 LINZUNZA UTILITY CLEARANCES KINDER MORGAN ENERGY Denied
05/05/2016 ZELIN CANCHOLA DOT TRAFFIC REVIEW Reqs Change May 4, 2016
ACTIVITY NUMBER: T16PI00005
PROJECT NAME: Banner UMC North campus
PROJECT ADDRESS: 3838 N Campbell Avenue
PROJECT REVIEWER: Zelin Canchola TDOT

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan therefore a revised plan is required for re-submittal. The following items must be revised or added to the plan. Include a response letter with the next submittal that states how all comments have been addressed.

1. Sheet 1 of 11 note 11 - Type C not applicable.

2. Sheet 8 of 11 - Replace type C with Type G reflective pavement markers.

Pavement marking checklist. - List quantities and descriptions for striping materials including number and type of RPMs, lineal footage, quantities on longitudinal and traverse striping, arrows and symbols.


If you have any questions, I can be reached at 520 837 6659 or zelin.canchola@tucsonaz.gov
05/17/2016 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved
05/17/2016 RICHARD LEIGH DOT ENGINEERING REVIEW Denied May 9, 2016

SUBJECT: Offsite Improvements for Banner UMC North Campus

PROJECT REVIEWER: Richard Leigh, TDOT, TDOT Eng. Review

RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to resubmittal. Please include a response letter addressing the following comments and return redlined drawings with subsequent submittal.

1. Include the plan number "U-2016-007" in the title block of each sheet.

2. Include the PIA activity number "T16PI00005 on cover sheet.

3. Sheet 5-7: Provide a profile view of roadway TDOT Office procedure No. 8-1552-002 Types of Sheets 2.E.

4. Sheet 2: Remove Detail 1, detail is not applicable.

5. Sheet 2: Revise detail 2 to indicate percent of grade of landing and ramp section. Additionally, provide details of the ramp curb.

6. Sheet 5: Revise drawing to eliminate proposed driveway entrance at +/- 11+00 Rt Allen Rd. Sewer manhole can be accessed from roadway.

7. Sheet 5-7: Revise drawing to depict a flared side on both sides of the curb access ramps per PC/COT Std. Dtl. 207 Sheet 4A.

8. Sheet 5: Label newly dedicated right-of-way along the north side of Allen Road with recordation information.

9. Sheet 5: Revise drawing to indicate the finished surface treatment details for the proposed median island.

10. Please Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsonaz.gov
05/24/2016 LINZUNZA DOT PERMITS & CODES REVIEW Denied Date: May 24, 2016
PROJECT NAME: Banner UMC North
PLAN #: U-2016-007
ACTIVITY NUMBER: T16PI00005
PROJECT REVIEWER: Tom Adkins, Construction Inspector, Engineering, City of Tucson DOT

Comments:

The TDOT Construction Inspection Unit has completed the review of the PIA plan and recommends resubmittal at this time. The following comments need to be addressed in the subsequent plan submittal. Please return redlined drawings with next submittal and reference PIA activity number on all correspondences.

1. Page 5 of 11 Median Detail; Note 12; This is not a 207 ramp; provide better drawing to assure ADA Compliance - Specific Detail for this "Ramp".

2. Page 6 of 11 Sta14+61.59; 18.00Lt to 16+66.89; 23.63lt - why is this sidewalk staying in place when it does not match dimensions of new sidewalk?

If you have any questions, I can be reached at 791-5100 or Tom.Adkins@tucsonaz.gov
05/24/2016 ERNIE ENCINAS DOT_ELEC REVIEW Denied Date: May 24, 2016
PROJECT NAME: Offsite Improvements for Banner UMC North Campus
PLAN #: U-2016-007 ACTIVITY NUMBER: T16PI00005
PROJECT REVIEWER: Paul Burton, Supervisor, TDOT Streets & Traffic Maint./Signal Electronics

Comments:
Sheet 10 of 12

Traffic Signal Note 14 should read "… outer cable jacket shall NOT be removed at the hand hole height…"

Traffic Signal Note 16 should read "… law enforcement officer SHALL PROVIDE POINT CONTROL DURING THE CHANGE-OVER TO THE NEW SIGNALS AT THE CONTRACTOR'S EXPENSE."

Conductor Note 4 should read "IMSA 16, 7, and 4 conductor cables…"

Identify existing poles D through J

Show existing video detection camera for eastbound traffic on luminaire mast arm of pole "D".

Install "Q" head on SEC "A" pole for SB phase 5 turns.

NEC - intercept existing conduits and extend to new #7 pull box with extension.

Include note that intersection shall require new 16 conductor IMSA to be run, un-spiced, from the controller cabinet to each pole's terminal block.

If you have any questions I can be reached at Paul.Burton@tucsonaz.gov
05/25/2016 GARY WITTWER DOT LANDSCAPE REVIEW Denied You must comply with all the requirement for placing irrigation lines under public roadways. Please call or e-mail me for those requirements.
05/25/2016 LINZUNZA PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
05/25/2016 LINZUNZA PIA COORDINATOR OUT TO CUSTOMER Completed