Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2016 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change Per Tucson Code 26-5.2(5) the floodplain water surface elevation may not rise more than a tenth of a foot.

Clogging of the box culvert with vegetation is also a concern and modeling of the area anticipated to experience obstruction from debris will be required with the rise limited to no more than a tenth of a foot.