Permit Review Detail
Review Status: Completed
Review Details: FLOODPLAIN
Permit Number - T16OT01377
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/28/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Reqs Change | Per Tucson Code 26-5.2(5) the floodplain water surface elevation may not rise more than a tenth of a foot. Clogging of the box culvert with vegetation is also a concern and modeling of the area anticipated to experience obstruction from debris will be required with the rise limited to no more than a tenth of a foot. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/12/2016 | LBOJORQ1 | OUT TO CUSTOMER | Completed |