Permit Number: T16OT00806
Parcel: 140190080

Address:
5344 S PARK AV

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - FLOODPLAIN

Permit Number - T16OT00806
Review Name: PLANS OK TO SUBMIT - FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved June 30, 2016
FLOODPLAIN USE PERMIT NO.: T16OT00806
ADDRESS: 5344 s Park, Tucson Arizona 85706
PROPERTY OWNER: PAG Desert Breeze LLC3
950 Echo Lane Ste 200, Houston, Texas 77024

The applicant is authorized to use a portion of the City of Tucson Flood Hazard Area per the Old Nebraska Wash delineation, specifically described as:

A portion of Parcel 140-19-0080, S2 NE4 Lot 6 Exc E45' & S 20' & W10' S2 & S2 & S65' N2 NE4 Lot 6 Exc E140' 5.43 AC

For the purpose of constructing electrical work.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and is particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Unified Development Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

The following 9 conditions apply to this permit:

1) This permit becomes invalid and is subject to additional floodplain review, if any required development changes the construction of the electrical work, or, if there is any further disturbance within the floodplain other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from the construction of electrical work within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson.
2) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.
3) All work shall conform to the approved site plan sheets for the construction of the electrical work, which are made part of this permit.
4) The electrical work must be constructed with all water sensitive components elevated 24" when located within the floodplain limits.
5) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T16OT00806 FOR INFORMATION PLEASE CALL 791-5550."
6) This Floodplain Use Permit and plans shall be kept in a readily accessible location on site at all times.
7) Any additional future disturbance of the floodplain shall have separate floodplain use permit applications submitted to this office for review and approval.
8) See the associated activity T16CM05070
9) This permit is specific to the improvements for 5344 S Park Ave as indicated on the approved plans. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit.

Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Planning & Development Services Department, Engineering Division. This permit may be renewed for up to one year, in the absence of Registered Plant authorization, at the sole discretion of the City Engineer or designated representatives.

This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions are not complied with, as set forth in this permit.

APPLICANT NAME: Arizona Electrical Solutions
ADDRESS: 333 N Wilmot Road # 340, Tucson, AZ 85749
PHONE: 520-308-6235
CONTRACTOR: TBD
ADDRESS: TBD
PHONE: TBD

(EXPIRATION DATE) Month: _06 Day: 30_ Year: 2017

SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.