Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16OT00783
Parcel: 13727638A

Address:
2085 W DREXEL RD

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T16OT00783
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved July 6, 2016
FLOODPLAIN USE PERMIT NO.: T16OT00783
ADDRESS: 2085 W Drexel Road Tucson, Arizona 85746
OWNER: Gregory and Bettina Beaucage
2085 W Drexel Road, Tucson Arizona 85746

The use a portion of the FEMA Special Flood Hazard Area Zone AO-1 per the Flood Insurance Rate Maps 04019C2270L, specifically described as:

A portion of Parcel 137-27638A; S200' N752.40' W429' NW4 1.96 AC SEC 10-15-13

For the purpose of constructing an elevated Single Family Residence.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Unified Development, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

This floodplain use permit is issued with the following 9 conditions:

1) This permit becomes invalid and is subject to additional floodplain review, if any required development changes the demolishing of the buildings, or, if there is any further disturbance within the floodplain other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from demolishing the commercial building within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson.

2) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.

3) For purposes of this permit the following flood elevations shall be used for the Single Family Residence:
Base Flood Elevation (BFE) = 1 (one) foot above the highest adjacent grade
Regulatory Flood Elevation (RFE) = 2 (two) feet above the highest adjacent grade
Single Family Residence is to have lowest finished floor elevated at or above the Regulatory Flood Elevation (RFE) and lowest point of any attached appliances is to be at or above the Regulatory Flood Elevation (RFE).

4) Floodplain Approval of elevation certificate, prepared by an Arizona State Registrant (Architect, Engineer or Land Surveyor), is required prior to the finished construction or Final Inspection (P2F). The Elevation Certificate must include the identity and elevation of the lowest service equipment/machinery servicing the single family residence, if applicable, as well as the identity and location of all other equipment/machinery servicing the single family residence.

5) Floodplain Approval of elevation certificate, prepared by an Arizona State Registrant (Architect, Engineer or Land Surveyor), is required prior to the pouring of the finished slab (P2S). The Elevation Certificate must include the identity and elevation of the lowest service equipment/machinery servicing the single family residence, if applicable, as well as the identity and location of all other equipment/machinery servicing the single family residence.

6) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T16OT00783 FOR INFORMATION PLEASE CALL 791-5550."

7) Any additional future disturbance of the floodplain shall have separate floodplain use permit applications submitted to this office for review and approval.

8) All work shall conform to the approved site plan, T16CM04880, which is made part of this permit.

9) This permit is specific to the improvements for 2085 W Drexel Road as indicated on the approved plans. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit.


This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions are not complied with, as set forth in this permit.

APPLICANT NAME: Greg Beaucage
ADDRESS: 2085 W Drexel Road, Tucson Arizona 85746
PHONE: 520-609-8879
CONTRACTOR: TBD
ADDRESS: TBD
PHONE: TBD

(EXPIRATION DATE) Month: 07 Day: 06 Year: 2017

SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/24/2016 RBENT2 OUT TO CUSTOMER Completed