Permit Number: T16CM09705
Parcel: 126071600

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T16CM09705
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: T16CM09705
375 N. Longfellow Avenu
Residential (1st Review)

TRANSMITTAL DATE: January 9, 2017


This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

1. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 9'-10" the required perimeter yard setback to the north and south property line is 6'-6", proposed is 6'-0".

2. The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall (UDC 6.4.5.C.1.a). Based on a wall height of 9'-10" the required front street perimeter yard setback is 20'-0", proposed front street perimeter yard setback from the garage to the street property line is 13'-0".

The process for to reduce perimeter yard setbacks is a Design Development Option (DDO). The DDO application can be found at https://www.tucsonaz.gov/files/pdsd/forms/2016_DDO_for_Setback_and_Height_UDC.pdf.

Once the above comments are addressed Zoning will provide an over-the-counter review.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
01/24/2017 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T16CM09705
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 with the following provisions: 1. A 4 square feet area for (meter, disconnect & inverter) equipment adjacent to the electrical service panel or near the proposed collector panel space. 2. The best roof space available for accommodating PV solar collector panels with capacity for collector dead loading (typically 4 lbs/SF). 3. A minimum 3,800 volt-ampere PV electrical load entry on the Service Load Calculation (Show as a continuous load of 15.8 A). 4. An Electrical Panel Schedule with a 240 volt circuit breaker space labeled "reserved for Photo Voltaic". See electrical comments.

SITE PLAN:

1. Indicate the required water pipe size from meter to the building, R106.1.1. Upgrade the ¾" to 1" as shown on sheet #7.

FLOOR PLANS:

1. Show a maximum ½" floor elevation change at a notated accessible route entrance on the floor plan, R106.1.1.
2. Show the location of a minimum 22" x 30" attic access. Attic access is required for areas exceeding 30 SQ FT with a minimum of 30" of headroom and located in a hallway or readily accessible space, R807.1.

FOUNDATION PLANS:

1. Indicate the direction of slope for the garage slab, R309.1.
2. Show compliance with termite treatment, R318.2.
3. Notate the grade away from foundations with a minimum 6" fall within the first 10', R401.3.

STRUCTURAL PLANS:

1. Provide a complete braced wall design, R602.10. Identify each wall line needed for enclosing a complete rectangle with sides no greater than 60', Figure R602.10.1.1. Place these lines no further than 4' from an actual parallel wall, so that corners are no further than 10' from a "qualifying" braced wall panel. An interior wall line is required for the 70' - 9" building.
2. Show alternate braced wall panel hold-downs with appropriate tie-down capacity dependent upon wall height, Table R602.10.6.1. Use greatest height for wall lines with different ceiling heights. The front facing bedroom #1 wall line requires hold-downs.

PLUMBING PLANS:

1. Show hot water pipe with minimum R-3 insulation, N1103.4.2.
2. Show the platform mounted water heater with a listed pan and ¾" drain line to a waste receptor or to the building exterior 6" above grade, P2801.5.
3. The revised City of Tucson Ordinance #11089 for gray water preparation requires a minimum of one compliant fixture. A single story dwelling with the clothes washer at an exterior wall requires two clothes washer standpipes. Provide one discharge opening plumbed through an exterior wall with an above grade stub-out for gray water surface distribution. Provide a second discharge opening plumbed to the building black line. See the detail at the PDSD web site.
4. Gray water systems may only receive waste discharge from bathtubs, showers, lavatories, clothes washers and laundry trays, AO101.9. Remove the gray drain lines from the food preparation sinks if installing a system exceeding the minimum requirement described in comment #4. Also, the washer requires a second drain branch line run directly to the building drain pipe.

MECHANICAL PLANS:

1. Provide (an HVAC system with) whole-house mechanical ventilation with continuous or a minimum controlled intermittent airflow rate, R303.4 & M1507.3. Show a source of outside supply air or continuous exhaust fan function.
2. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical system calculations may be provided by deferred submittal. The deferred calculations must be approved through revision process prior to mechanical inspections.

ELECTRICAL PLANS:

1. Show compliance with the City of Tucson Ordinance #10549 for future Photo Voltaic on the panel schedule and electrical load calculation.
2. Smoke alarms are required outside each separate sleeping area, R314.3.2. In addition to within bedrooms add a detector in the hallway to bedroom #1/2.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 and walls R=13. Show the maximum "U" factors of the windows and doors on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.25, N1102.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/27/2017 ARUIZ1 OUT TO CUSTOMER Completed