Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM09664
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2017 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/06/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 01/06/2017 | ARUIZ1 | WWM | REVIEW | Needs Review | |
| 01/06/2017 | KROBLES1 | FIRE | REVIEW | Needs Review | |
| 12/28/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/28/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 12/28/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 12/28/2016 | ROBERT SHERRY | WATER | REVIEW | Needs Review | |
| 12/28/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 12/28/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review |