Permit Number: T16CM09556
Parcel: 11706168A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM09556
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The generic water drop schematics do not provide any information regarding the number of appliances to be directly-connected to cold water, hot water, or softened hot water. [Initial comment: Provide the water schematic referenced in the plumbing fixture schedule. Verify that each appliance directly connected to water has a backflow prevention device. Reference: Section 107.2.1, IBC 2012 and Sections 608.1 and 608.16.10, IPC 2012.]