Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM09556
Parcel: 11706168A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM09556
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2017 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed PASS PER ENEWCOMB
01/03/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/03/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Completed
01/03/2017 ROBERT SHERRY WATER REVIEW Completed
01/03/2017 GERRY KOZIOL WWM REVIEW Completed
01/06/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The 2012 IECC is the currently adopted energy code (see sheet P0.1).
2. Provide the water schematic referenced in the plumbing fixture schedule. Verify that each appliance directly connected to water has a backflow prevention device. Reference: Section 107.2.1, IBC 2012 and Sections 608.1 and 608.16.10, IPC 2012.
3. If the ice maker does not have a listed, integral backflow preventer or an integral air gap conforming to Section 608.13.1, IPC 2012, specify the backflow prevention device to be installed. Reference: Sections 608.1 and 608.3, IPC 2012.
12/22/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
12/22/2016 ANDREW CONNOR ZONING REVIEW Approved
12/22/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/23/2016 MARTIN BROWN FIRE REVIEW Approved