Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM09549
Parcel: 115072810

Address:
101 W ADAMS ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T16CM09549
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2017 KROBLES1 ZONING REVIEW Reqs Change COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the C-3 zone (UDC 4.7.22). A single-family residence is a permitted use in this zone (Table 4.8-2).

Within established areas, the minimum required front street perimeter yard is 20 feet or one and one-half the height of the proposed wall (H), measured from the street property line, whichever is greater, up to a maximum of 90 feet. UDC 6.4.5-C.1.a

The minimum setback to a side street property line is ten (10) feet (UDC Section 6.4.5.C.1.b).

The applicant is proposing additions to a single family residence on a C-3 zoned property. The required front yard set-back is 20' proposed is 17' The required side street set-back is 10' the proposed is 7'
08/01/2017 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T16CM09549
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SECTIONS - DETAILS:

1. The residence framing plan on A-7 shows inconsistent references at the living room extension, R106.1.1. Update detail 5/A6 or section B/A-6 with an unvented roof, or a vented roof assembly.
2. The residence framing plan on A-7 shows reference 10/A6 at the dining room, R106.1.1. Provide the detail.

ELECTRICAL PLANS:

1. Update the sub panel rating shown on the riser diagram, R106.1.1.
2. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
08/15/2017 LOREN MAKUS ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2017 QJONES1 APPROVAL SHELF Completed
08/25/2017 QJONES1 OUT TO CUSTOMER Completed
08/25/2017 QJONES1 REJECT SHELF Completed