| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/17/2017 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/17/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE. #1. THE REVISED SUBMITTAL DID NOT PROVIDE ENOUGH INFORMATION TO VERIFY COMPLIANCE THE TUCSON OUTDOOR LIGHTING CODE. PROVIDE SHIELDING INFORMATION FOR THE RETROFITTED EXTERIOR LIGHTING, FLUORESCENT AND LED. IF NOT FULLY SHIELDED ( FULL CUT-OFF ) AS DEFINED PER CHAPTER2, PROVIDE LUMEN CALCS AND VERIFY COMPLIANCE WITH LUMEN CAPS PER TABLE 401.1. REF: TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE |
| 02/17/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 6; SHEET A1.1; FLOOR PLAN: THE NEW WALL ADDED TO THE CORRIDOR OUTSIDE THE RESTROOMS APPEARS TO HAVE CREATED A DEAD END CORRIDOR THAT EXCEEDS THE REQUIREMENTS OF THE IBC SECTION 1018.4. PLEASE VERIFY. THIS CAN NOT BE CONSIDERED AS AN EXISTING NON-CONFORMING CONDITION SINCE THE NEW WALL IS CREATING THE DEAD END. PLEASE REVISE. |
| 02/17/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed |