Permit Number: T16CM09514
Parcel: 11613193F

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM09514
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/17/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 6; SHEET A1.1; FLOOR PLAN: THE NEW WALL ADDED TO THE CORRIDOR OUTSIDE THE RESTROOMS APPEARS TO HAVE CREATED A DEAD END CORRIDOR THAT EXCEEDS THE REQUIREMENTS OF THE IBC SECTION 1018.4. PLEASE VERIFY. THIS CAN NOT BE CONSIDERED AS AN EXISTING NON-CONFORMING CONDITION SINCE THE NEW WALL IS CREATING THE DEAD END. PLEASE REVISE.
02/17/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE.
#1. THE REVISED SUBMITTAL DID NOT PROVIDE ENOUGH INFORMATION TO VERIFY COMPLIANCE THE TUCSON OUTDOOR LIGHTING CODE. PROVIDE SHIELDING INFORMATION FOR THE RETROFITTED EXTERIOR LIGHTING, FLUORESCENT AND LED. IF NOT FULLY SHIELDED ( FULL CUT-OFF ) AS DEFINED PER CHAPTER2, PROVIDE LUMEN CALCS AND VERIFY COMPLIANCE WITH LUMEN CAPS PER TABLE 401.1.
REF: TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE
02/17/2017 STEVE SHIELDS ZONING REVIEW Approved