Permit Number: T16CM09514
Parcel: 11613193F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM09514
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2017 MARTIN BROWN FIRE REVIEW Approved
01/13/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Wendy's Remodel & Façade Changes
T16CM09514
Building Plan (1st Review)

TRANSMITTAL DATE: January 13, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. As changes to existing façade are proposed which appear to increase the height of the structure. The proposed changes are required to meet street perimeter yard setbacks. W. Saint Mary's Road is designated as an Arterial, Scenic route on the Major Streets and Routes Map (MS&R) therefore the street perimeter yard is based on UDC Article 5.3.5.A. Provide a development package, meeting the requirements of Administrative Manual 2-06 that demonstrates that the requirements of UDC Article 5.3.5.A are met.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
01/24/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/24/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change All water outlets or direct-connections of water to an appliance that is being relocated (e.g. tea dispenser) shall be protected against backflow. Specify the device to be used for each outlet or appliance connection. Reference: Sections 608.15 and 608.16, IPC 2012.
01/24/2017 ROBERT SHERRY WATER REVIEW Completed
01/27/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G1.1; CODE DATA: PLEASE INDICATE ON THE DRAWINGS THE EDITION (DATE) OF THE APPLICABLE CODES USED ON THIS PROJECT.
2. SHEET G1.1; CODE DATA: PLEASE REVISE THE ACCESSIBILITY CODE TO THE 2009 ICC/ANSI A117.1.
3. SHEET G1.1; CODE DATA: PLEASE INCLUDE THE REQUIREMENT FOR A SERVICE SINK IN THE PLUMBING REQUIREMENTS.
4. SHEET C1.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES ON THE SITE PLAN.
5. SHEETS D1.1, A1.1, A1.2, AND A1.3; FLOOR PLANS: PLEASE PROVIDE A NORTH ARROW ON THE PLANS.
6. SHEET A1.1; FLOOR PLAN: THE NEW WALL ADDED TO THE CORRIDOR OUTSIDE THE RESTROOMS APPEARS TO HAVE CREATED A DEAD END CORRIDOR THAT EXCEEDS THE REQUIREMENTS OF THE IBC SECTION 1018.4. PLEASE VERIFY.
7. SHEET A1.1; FLOOR PLAN: PLEASE INCLUDE A DETAIL OR A NOTE ON THE DRAWINGS INDICATING THE NEW COUNTERTOP (SEE GENERAL NOTE 15) MEETS THE ACCESSIBILITY REQUIREMENTS OF THE ICC/ANSI SECTION 904 FOR COUNTER HEIGHT AND APPROACH.
8. SHEET A1.1; FLOOR PLAN: SINCE THE SEATING LAYOUT HAS BEEN CHANGED FROM THE EXISTING, PLEASE PROVIDE A CALCULATION ON THIS SHEET INDICATING THE TOTAL NUMBER OF SEATS IN THE DINING AREAS, AND THE NUMBER OF ACCESSIBLE SEATS REQUIRED BY THE IBC SECTION 1109.11. INDICATE AND NOTE THOSE SEATS AND TABLES ON THE PLAN.
9. SHEET A1.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE EQUIPMENT SCHEDULE.
10. SHEET A1.1; FLOOR PLAN: PLEASE INDICATE A DETAIL OR A NOTE ON THE DRAWINGS INDICATING THE NEW INTERNET BAR MEETS THE ACCESSIBILITY REQUIREMENTS OF THE ICC/ANSI SECTION 902 FOR THE DINING/WORKING SURFACE HEIGHT AND CLEAR FLOOR SPACE.
11. SHEET A3.1; SECTIONS 01 AND 02: A NOTE INDICATES A PRE-MANUFACTURED BLADE TO HAVE ENGINEERED SHOP DRAWINGS. PLEASE FOLLOW THE REQUIREMENTS OF THE IBC SECTION 107.3.4.1 FOR DEFERRED SUBMITTALS.
12. SHEET A3.2; SECTION 01: THIS IS ACTUALLY A PLAN. PLEASE REVISE THE TITLE. ADD A SECTION THROUGH THIS PLAN, AND INDICATE THE NEW FOUNDATION/SLAB THAT SUPPORTS THIS ADDITION. INDICATE THE FOUNDATION/SLAB SIZE, DEPTH BELOW GRADE, REINFORCING, AND CONNECTION OF THE NEW STUD WALL TO THE FOUNDATION/SLAB. THE SECTION INDICATES TO SEE SHOP DRAWINGS. IS THIS A PRE-FABRICATED WALL? PLEASE CLARIFY.
13. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/03/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE.
#1. There is no response or compliance on the plans for the Outdoor Lighting Code requirements as requested per the first plan review comment.
Ref: Plan Sheet E3. The removal of the exterior fluorescent fixtures to be replaced with LED lighting around the building and the re-lamping of the other exterior fluorescent fixtures shown outside the vestibule, requires compliance for lumen cap, and color temperature output, shielding requirements, inventory, complete luminaire schedules, as outlined per sec. 104, and other sections of the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE that may apply.
Ref: 2012 IBC107.2.1, 2011 NEC, CITY OF TUCSON COMMERCIAL PLAN SUBMITTAL REQUIREMENTS, TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE.
Dan.santacruz@tucsonaz.gov
02/07/2017 LOREN MAKUS ENGINEERING REVIEW Approved
02/15/2017 GERRY KOZIOL WWM REVIEW Approved