Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T16CM09484
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | We seem to have a failure to communicate. The first requirement is for the sensor faucet to have a delivery cycle that lasts for at least 10-seconds (Section 606.4, ICC/ANSI A117.1-09). The second requirement is for the sensor faucet to deliver no more than 0.25 gallons per operating cycle (Section 416.6, IPC 2012, as amended by the City of Tucson). With a flow rate of 0.5 gallons per minute, the longest cycle time should be 30-seconds; therefore, set the automatic time out on the faucet for 30-seconds. [Second comment: Specify that the proposed lavatory faucet (T&S Brass EC-3102-VF5-TMV) will have an automatic time out set for a maximum of 30-seconds.] [Initial comment: Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.] |
| 04/19/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/24/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/28/2017 | ARUIZ1 | WWM | REVIEW | Needs Review |