Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T16CM09470
Parcel: 114469500

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM09470
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET PV-2; SITE PLAN: PLEASE INDICATE ON THE PLAN THE DISTANCE FROM THE EDGE OF THE NEW PARKING STRUCTURE ROOF TO THE EXISTING BUILDING. IN ADDITION, INDICATE ON THE PLAN THE DISTANCE FROM THE FACE OF THE NEW PARKING STRUCTURE COLUMN TO THE EXISTING BUILDING. THE CITY OF TUCSON REQUIRES A MINIMUM FIRE SEPARATION DISTANCE OF 24" FROM THE NEW ROOF PROJECTION TO THE EXISTING BUILDING, AND A MINIMUM FIRE SEPARATION DISTANCE OF 5'-0" FROM THE FACE OF THE NEW STRUCTURAL SUPPORT TO THE EXISTING BUILDING. IF THE DISTANCES ARE LESS THAN THOSE REQUIRED, THE NEW STRUCTURE MUST BE FIRE RESISTANCE RATED.
2. SHEET S1; GENERAL STRUCTURAL NOTES (FOUNDATIONS): THE REFERENCES TO THE IBC SECTION 1804 FOR DRILLED PIER FOOTING DESIGN, 1804.3.1 FOR LATERAL BEARING PRESSURE, 1805.7.2.2 FOR DRILLED PIER CONSTRAINED DESIGN, AND 1804 FOR SPREAD FOOTING DESIGN ARE NOT CORRECT UNDER THE 2012 IBC. PLEASE REVISE THOSE REFERENCES.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/30/2016 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/24/2017 KROBLES1 OUT TO CUSTOMER Completed