Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM09470
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/20/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET PV-2; SITE PLAN: PLEASE INDICATE ON THE PLAN THE DISTANCE FROM THE EDGE OF THE NEW PARKING STRUCTURE ROOF TO THE EXISTING BUILDING. IN ADDITION, INDICATE ON THE PLAN THE DISTANCE FROM THE FACE OF THE NEW PARKING STRUCTURE COLUMN TO THE EXISTING BUILDING. THE CITY OF TUCSON REQUIRES A MINIMUM FIRE SEPARATION DISTANCE OF 24" FROM THE NEW ROOF PROJECTION TO THE EXISTING BUILDING, AND A MINIMUM FIRE SEPARATION DISTANCE OF 5'-0" FROM THE FACE OF THE NEW STRUCTURAL SUPPORT TO THE EXISTING BUILDING. IF THE DISTANCES ARE LESS THAN THOSE REQUIRED, THE NEW STRUCTURE MUST BE FIRE RESISTANCE RATED. 2. SHEET S1; GENERAL STRUCTURAL NOTES (FOUNDATIONS): THE REFERENCES TO THE IBC SECTION 1804 FOR DRILLED PIER FOOTING DESIGN, 1804.3.1 FOR LATERAL BEARING PRESSURE, 1805.7.2.2 FOR DRILLED PIER CONSTRAINED DESIGN, AND 1804 FOR SPREAD FOOTING DESIGN ARE NOT CORRECT UNDER THE 2012 IBC. PLEASE REVISE THOSE REFERENCES. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
12/30/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/24/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |