Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM09445
Parcel: 141186310

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM09445
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/27/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Condensate drains may not terminate over a roof drain unless the roof drain terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. The roof drains appear to terminate over paved areas. [Initial comment: Condensate drains shall be terminated at an approved disposal location. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.]
2. Refer to equation 4-8, IMC 2012; the uncorrected outside air quantity (Vou) is divided by the system ventilation efficiency (Ev) to determine to determine the outdoor air intake flow rate (Vot). Reference: Section 403.3.2.3.4, IMC 2012. [Initial comment: Provide calculations demonstrating adequate ventilation using the current code, IMC 2012. Use a zone air distribution effectiveness value of 0.8 for a ceiling supply, ceiling return using a gas-fired furnace. UNITS AC-6, AC-7, and AC-8 should be considered as serving multiple zone Reference: Section 403.2 and 403.3.2.3, IMC 2012.]
3. Section 403.7, IMC 2012 calls for the HVAC systems to be balanced so that the correct amount of outside air will be delivered. Calling for a 5-ton unit to deliver only 1200 CFM will not deliver the outside air for very long. See also Section 301.7, IMC 2012. [Initial comment: Verify the balancing data for AC-6, AC-7, EF-1, and EF-2 and coordinate the results with the scheduled air flow rates. Reference: Section 107.2.1, IBC 2012 and Section 403.7, IMC 2012.]
4. Comment not addressed; no new COMcheck envelope compliance certificate has been submitted. [Initial comment: Provide documentation to show that the building envelope was constructed using the components described in the submitted COMcheck Envelope Compliance Certificate. Note: the submitted Envelope Compliance Certificate calls for high efficiency HVAC systems to satisfy the requirements of Section C406, IECC 2012 but both the Mechanical and Interior Lighting Compliance Certificates utilized reduced interior lighting power; coordinate. Reference: Section 107.2.1, IBC 2012.]
5. Revise the Mechanical COMcheck to agree with the scheduled HVAC equipment. [Initial comment: Revise the Mechanical Compliance Certificate to include both 3-ton AC units. Reference: section 107.2.1, IBC 2012.]
6. Required energy efficiencies for units with nominal capacities of 5-tons or smaller are only shown as SEER values in the IECC. Show the SEER rating for the applicable units. [Initial comment: The EER values for the 5-ton, 4-ton, and 3-ton AC units as shown on the Mechanical Compliance Certificate do not agree with the scheduled SEER values on sheet M2.0; coordinate. Reference: Section C403.2.3, IECC 2012 and Section 107.2.1, IBC 2012.]
02/27/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/27/2017 ROBERT SHERRY WATER REVIEW Reqs Change Comment not addressed. [Initial comment: Coordinate the location of the water meter and the reduced pressure backflow prevention assembly with the civil drawings. Water meters are located at the property line or within an easement. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf]
02/27/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Specify the maximum cycle time required to ensure the delivery of 0.25 gallons per cycle with a minimum cycle time of 10-seconds for accessibility. [Initial comment: Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the cycles of the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.]
2. The specified water heater is bottom-fed. Either revise the specification or the detail. [Initial comment: Provide an approved vacuum relief valve for the scheduled bottom-fed water heater which is located above the fixture outlets. Reference: Section 504.2, IPC 2012.]
3. The 3" horizontal drain formed by fixture drains for P-3H and FD-1 requires a clean out. [Initial comment: Provide a cleanout for the 3" fixture branch located in the men's restroom (115). Reference: Section 708.7, IPC 2012.]
03/08/2017 ARUIZ1 ZONING REVIEW Needs Review