Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM09445
Parcel: 141186310

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM09445
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Ross Dress for Less - Houghton Town Center
T16CM09445
Building Plan (1st Review)

TRANSMITTAL DATE: January 9, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Per Tentative Plat S11-044 Sheet 8 the Long term bicycle parking is to be provided within the building. Demonstrate on the plan how this is done.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
01/12/2017 MARTIN BROWN FIRE REVIEW Approved
01/20/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Sheet P1.0 is stamped, "PRELIMINARY NOT FOR CONSTRUCTION." Preliminary documents are not acceptable for review.
2. Provide a copy of the shell building plans and the site plans for reference. Reference: Section 107.2.1, IBC 2012.
3. Clarify the method used to determine the sizes of the gas pipes; the notes state that the pipe was sized based on Table 402.4(3), IFGC 2009 (<2 PSIG with a pressure drop of 0.5 PSIG) but the pipe sizes do not appear to correspond to those criteria. The code currently in use is the 2012 IFGC. Reference: Sections 402.1 and 402.3, IFGC 2012.
4. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the cycles of the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
5. Provide an approved vacuum relief valve for the scheduled bottom-fed water heater which is located above the fixture outlets. Reference: Section 504.2, IPC 2012.
6. Clarify the specification for the tempered water mixing valve for the lavatories. Detail 4/P2.0 calls out a different valve than note 9 of the plumbing fixture table. Reference: Section 107.2.1, IBC 2012 and 607.1.2, IPC 2012.
7. Provide a cleanout for the 3" fixture branch located in the men's restroom (115). Reference: Section 708.7, IPC 2012
01/20/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Condensate drains shall be terminated at an approved disposal location. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
2. Provide exhaust for the men's fitting room (106). Reference: Section 403.3, IMC 2012.
3. Provide calculations demonstrating adequate ventilation using the current code, IMC 2012. Use a zone air distribution effectiveness value of 0.8 for a ceiling supply, ceiling return using a gas-fired furnace. UNITS AC-6, AC-7, and AC-8 should be considered as serving multiple zone Reference: Section 403.2 and 403.3.2.3, IMC 2012.
4. Verify the balancing data for AC-6, AC-7, EF-1, and EF-2 and coordinate the results with the scheduled air flow rates. Reference: Section 107.2.1, IBC 2012 and Section 403.7, IMC 2012.
5. Provide documentation to show that the building envelope was constructed using the components described in the submitted COMcheck Envelope Compliance Certificate. Note: the submitted Envelope Compliance Certificate calls for high efficiency HVAC systems to satisfy the requirements of Section C406, IECC 2012 but both the Mechanical and Interior Lighting Compliance Certificates utilized reduced interior lighting power; coordinate. Reference: section 107.2.1, IBC 2012.
6. Revise the Mechanical Compliance Certificate to include both 3-ton AC units. Reference: section 107.2.1, IBC 2012.
7. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
8. The EER values for the 5-ton, 4-ton, and 3-ton AC units as shown on the Mechanical Compliance Certificate do not agree with the scheduled SEER values on sheet M2.0; coordinate. Reference: Section C403.2.3, IECC 2012 and Section 107.2.1, IBC 2012.
9. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
10. Show how the HVAC system is capable of relieving excess outdoor air from the building during economizer operation. Reference: Section C403.3.1.1.4, IECC 2012.
01/20/2017 ROBERT SHERRY WATER REVIEW Reqs Change Coordinate the location of the water meter and the reduced pressure backflow prevention assembly with the civil drawings. Water meters are located at the property line or within an easement. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
01/26/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A0.0; CODE SUMMARY: PLEASE ADD THE 2009 ICC/ANSI A117.1 ACCESSIBILITY CODE TO THE LIST.
2. SHEET A1.0; FLOOR PLAN: PLEASE PROVIDE A DETAIL ON THE DRAWINGS INDICATING THE CASH WRAP COUNTER AND THE CHECK OUT COUNTERS MEET THE ICC/ANSI ACCESSIBILITY REQUIREMENTS OF SECTION 904.3.
3. SHEET A1.0; FLOOR PLAN: PLEASE PROVIDE A DETAIL ON THE DRAWINGS INDICATING THE ACCESSIBLE DRESSING ROOM BENCHES MEET THE ICC/ANSI ACCESSIBILITY REQUIREMENTS OF SECTION 903.
4. SHEET A1.1; LIFE SAFETY PLAN: THE EXITS INDICATE THE ALLOWABLE NUMBER OF OCCUPANTS PER EXIT. PLEASE INDICATE THE ACTUAL NUMBER OF OCCUPANTS AT EACH EXIT (670 TOTAL).
5. SHEET A4.0; ENLARGED RESTROOM PLAN: THE ELEVATION INDICATORS ON THE PLAN SHOULD INDICATE 5/A4.0 IN THE MEN'S RESTROOM AND 6/A4.0 IN THE WOMEN'S RESTROOM. PLEASE VERIFY.
6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/26/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
02/01/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS. ALSO PROVIDE A WRITTEN RESPONSE.
#1. The electrical registrant stamp on the electrical plans is not legible, and there is no expiration date.
#2. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code. This code can be down loaded from www.tucsonaz.gov/pdsd.
Ref: 2012 IBC 107.2.1, TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE, ARIZONA REVISED STATUTES 32-125, R4-30-304.
Dan.santacruz@tucsonaz.gov
02/15/2017 GERRY KOZIOL WWM REVIEW Approved